Unlike existing fire doors with only 1 hour of non-fire resistance performance, the smart fire door has 3 hour of non-fire resistance performance, which has been certified by domestic and overseas (UL) agencies. Its performance is 3 times more than existing fire doors. The ‘New 3Hr Fire-proof glass Solution’, a new type of fire-resistant glass, provides safety from fire and open field of view compare to existing fire compartments. Unlike existing fire doors, which have been blocked, fire-resistant glass can be used to identify situations in indoor fire and fire protection compartments. It has been approved by the US UL for a fireproof performance that does not destroy for more than 3 hours.

Product Information – Single Door

Maximum size 1200 x 2400 (mm)
Fire rating ANSI / UL 10C &CAN / ULC-S104 / 3hours
Performance test Refractory / air leakage / door set / hose stream test
Style Flush Style, Flush Style with Vision Panel
Type Single Door
Certifications

Product Information – Double Door

Maximum size 2400 x 2400 (mm)
Fire rating ANSI / UL 10C & CAN / ULC-S104 / 3hours
Performance test Refractory / insulation / door set / water injection test
Style Flush Style, Flush Style with Vision Panel
Type Double Door
Certifications

FIRE DOOR Styles and Colors

Flush Style with Vision Panel
Powder Finish
(Matt Red Color)

Flush Style
Powder Finish
(Matt Gray Color)

Embossed Style
Wood Grain Finish
(Maple Color)

Flush Style with Vision Panel Double Door
Powder finish
(Matt Red Color)

SMART FIRE DOOR / Components

Smart Fire Door

안전 방재 전문 기업이 만든 방화문

Characteristics
Fire door over fire door!
Reliable fire door acquired UL & KS certification

Performance
Fire resistance 180min
Air leakage 0.0 m³ / min m²

Maximum size
Single 1200mmX2400mm
Double 2400mmX2400mm

Material
GLASS, STAINLESS STELL, STEEL

Fire Door Rating Test (KS 180 min, UL 3Hr Rating) – 1

Fire Door Rating Test (KS 180 min, UL 3Hr Rating) – 1

Fire Resistance Test

Air Leakage Test

Hose Stream Test

Door Performance Test

Door Components

NAGA Fire Steel Door

Door size
Large : 900~1,200(W) x 2,000~2,400(H)
Medium : 600~800(W) x 2,000~2,100(H)
Small : 400~600(W) x 1,700~1,900(H)

Main terms
ㆍ KS A type fire door, 3-hour non-fire, 13-minute fire resistance & UL 3-hour certification
ㆍ Vision (glass) _UL parts: 127 (W) x 508 (H) x 5 (T) (mm)
ㆍ BB Hinge_UL parts: 114.3 (W) x 114.3 (H) x 3.0 (T) (mm)
ㆍ Fire Exit Device (Rim type) or Fire Exit Device (Mortise Lock type) / Door Leaf / Door Frame / Smoke seal_UL 3 hour parts certification
ㆍ Escutcheon Lever Trim: Used in combination with Fire Rim Exit Devlce
ㆍ Automatic closing device: KFI performance certification, 1 hour fireproof certification, door opening angle (60 ~ 180 ℃) low load type capacity (40 ~ 65kg), high load type capacity (15 ~ 120kg)
ㆍ Temperature sensor: waterproof / dustproof, temperature measurement range (-10 ~ 100 ℃), output 4 ~ 20mA

Components of fire door set
Fire Exit Device (Rim type) or Fire Exit Device (Mortise Lock type), BB Hinge, Temperature Sensor, Escutcheon Lever Trim. Automatic Closing Device, etc.

Fire door set components and main specifications

(Fire door set components are set up from 1 to 8, depending on the situation.)

1. Fire Exit Device(Rim Type)

  • Optional upon customer request
  • Certification: UL 3-hour parts certification
  • Material: Steel, Aluminum Finish or Stainless steel cover
  • Size

    – 1,219x57x64 (mm) Door W: 1,060 ~ 1,200 (mm)
    – 914x57x64 (mm) Door W: 600 ~ 1,050 (mm)
    – Head cover: 154x55x65 (mm)

2. Fire Exit Device(Mortise Lock type)
Basic Specification

  • Certification: UL 3-hour parts certification
  • Material: stainless steel
  • Size: 101 (W) x202 (H) x31.5 (D) (mm)

3. Escutcheon Lever Trim

  • Fire Rim Exit Device and set components
  • Material: zinc alloy
  • Size: 64 × 231 (mm)

4. BB Hinge

  • Certification: UL 3-hour parts certification
  • Material: stainless steel
  • Size: 114.3 (W) x 114.3 (H) x 3.0 (T) (mm)
  • The amount is different according to the size of fire door.

5. Smoke Seal

  • Certification: UL 3-hour parts certification
  • Material: elastomeric PVC
  • Size: 12x12x0.8T (mm)

6. Automatic Closing Device

  • Certification: KFI performance certification, 1Hr fire resistance certification
  • Components: control 1EA, closure 1EA
  • Material: aluminum alloy for die-casting
  • Voltage and current: 24V, 10 to 150mA
  • Functions
    – Motor type
    – Door opening angle (60 ~ 180˚) / Type selection according to load capacity of fire door
    – Low load type capacity (40 ~ 65kg)
    – High load type capacity (15 ~ 120kg)

7. Temperature sensor

  • Waterproof / dustproof type
  • Size: 120x80x60 (mm)
  • Temperature measurement range: -10 to 100 ℃
  • Output: 4 to 20A

8. 설비용 자재

  • Terminal box (terminal block included_20P)
    – Material: Steel
  • Cable
    – FS, 0.3SQ, 3C :3M
    – 20AWG, 6C, :5M
    – TFR-3, 1.5SQ, 8C :2M
    – TFR-3, 2.5SQ, 3C :3M
  • Flexible conduit (with connectors & saddles)
    – 10mm:3M
    – 12mm:3M
    – 28mm:5M

IOT Smart Collector

NAGA Smart Wise 1A

  • NAGA IoT Device
  • Material: Stainless Steel
  • Certifications: IP67, Kc, KT QAT
  • Size: 210 * 160 * 75 (mm) (Without Antenna)
  • LTE-M Cat.1
  • Digital Input: 5Ch (N / O)
  • Digital Output: 2Ch, 24V / 1A
  • Analog Input: 4 ~ 20mA Input 1Ch
  • Analog Digital Converter: 3Ch (DC Voltage Input)
  • Built-in temperature / humidity sensor
  • Network test included (cable, device installation are not included)

Fire Door Power Supply

NAGA Power Supply

  • Size: 230 * 300 * 70, 1.0T (mm)
  • Input Voltage: AC 85 ~ 264V / 47 ~ 63Hz
  • Output Voltage: DC24V 4.5A
  • Output Voltage ADJ. RANGE: 21.6V ~ 28.8V
  • RATED POWER: 108W
  • Battery Specification: 1.3Ah (Ni-Cd)
  • Material: Steel

Smart IoT Fire Door Control Software

Screen configuration may vary depending on your needs

Fire Door Control Software

  • SW name: NAGA FDM
  • Version: 1.0
  • Main functions:
  • Fire door IoT transmission / reception function
  • Fire signal interlocking fire door automatic closing function
  • Fire door manual closing function
  • Fire alarm monitoring function (monitor development status)
  • Temperature around fire door monitoring
  • Control system power supply monitoring function